AKYES-261H125
Keywords:
AKYES-261H125
Classification:
Details
Integrated Design Philosophy
The cabinet incorporates a comprehensive integration of battery packs,Battery Management System(BMS), Energy Management System(EMS),modular Power Conversion System(PCS),liquid cooling system,and fire suppression system.With 261kWh capacity and 125kW power output,its modular design enables flexible capacity expansion,ensuring adaptability to diverse application scenarios.
Safety &Reliability
High-quality LiFePO4 battery cells
Integrated liquid cooling system ensures optimal thermal management
IP54 rating for reliable operation in harsh environments
PCS-battery string design eliminates circulating currents,enhancing system stability
Modular architecture simplifies installation,maintenance,and capacity expansion
Ultra-compact design with 50%space-saving footprint compared to traditional systems
Pre-assembled delivery reduces on-site installation costs and commissioning time
125KW/261kWh Automatic Coolant Replenishment System Solution
Cost Efficiency
Multifunctional operation:Grid-tied/off-grid seamless switching,dynamic capacity expansion,and peak shaving Compact &lightweight design minimizes space requirements and installation expenses
Extended lifespan with low failure rates and reduced maintenance costs
Maximizes renewable energy utilization to lower electricity bills
Hydro Core
| Battery Data | |
| Product Model | AKYES-261H125 |
| Battery Technology | LFP |
| Rated Capacity | 314Ah |
| Configuration method | 1P52S * 5 |
| Rated Voltage | 832V |
| Voltage Range | 741~949V |
| Rated Energy | 261.2kWh |
| Charging/Discharging Rate | ≤0.5P |
| Max Charge/Discharge Current | 168A |
| Battery Life Cycle | ≥8000(@25℃,0.5C/0.5C 70EOL) |
| Maximum System Efficiency | 98% |
| PCS Data(DC) | |
| Opreating Voltage Range(V) | 580~1000V |
| Max. DC Curent(A) | 168A |
| Rated AC Power(kw) | 125kW |
| Max. AC Power(KW) | 137.5kW |
| Max AC Current(A) | 200A |
| Rated AC Line Voltage(V) | 340Vac~440Vac |
| Rated AC Line Frenquency (Hz) | 50Hz/60Hz±2.5Hz |
| Grid Connection Data (On Grid) | |
| AC Output Power | 125kW |
| Max. AC Output Power | 137.5kW |
| Nominal AC Voltage(V) | 340Vac~440Vac |
| Nominal Grid Frequency / Grid Frequency Range(Hz) | 50Hz/60Hz±2.5Hz |
| THDi | ≤5% |
| Rated Power Factor | >0.99 |
| Adjustable Power Factor | ﹣0.99~﹢0.99 |
| AC Output Topology | Three-phase four-wire system |
| Grid Connection Data (off Grid) | |
| AC Output Power | 125kW |
| Max. AC Output Power | 137.5kW |
| Nominal AC Voltage (V) | 400Vac |
| AC Voltage THD | ≤3%(Linear load) |
| Nominal Grid Frequency / Grid Frequency Range(Hz) | 50Hz/60Hz |
| Max. AC Output Current (A) | 200A |
| AC Output Topology | Three-phase four-wire system |
| Temperature Control Parameters | |
| Rated Cooling Capacity | 5000W |
| Rated Cooling Power | 2100W |
| Rated Heating Capacity | 2000W |
| Coolant Type | Ethylene Glycol Solution |
| Refrigerant | R314a |
| Operating Temperature Range | -30~55℃ |
| General Data | |
| Dimensions (W"D*H) | 1000*1590*2350mm |
| Weight | <2600kg |
| Protection | IP54 |
| Operating Temperature Range | -20~+50 |
| Relative Operating Humidity | RH≤95%,No Condensation |
| Operating Altitude | <2000m |
| Cooling Method | Liquid Cooling |
| Fire Suppression System | Aerosol |
| Communication interfaces | RS485、CAN |
| Communication Protocols | Modbus、IEC104 |